Amplon RT Series
WARNING:
Ú
Please refer to the table below to select the charge current for 5kVA/ 6kVA/ 10kVA UPS.
Ú If you need to modify the charge current default setting,
please contact your local
dealer or customer service.
3. Low Battery Shutdown:
1) 5kVA/ 6kVA: 168V±3%
2) 10kVA: 210V±3%
4. The number of batteries:
1) 5kVA/ 6kVA: 12V x 16PCS
2) 10kVA: 12V x 20PCS
z
External Battery Pack:
1. To increase the battery backup time, you can connect several external battery packs to the
UPS.
2. Delta external battery pack (optional):
Please refer to the Quick Guide, User Manual or Installation & Operation Guide included in
the package of the external battery pack.
3. Non-Delta external battery pack:
When connecting a non-Delta external battery pack with the UPS, please install the fuse
or DC breaker first. Do not use an AC breaker. Please follow the actual discharge current
to decide the breaker’s current capacity.
1)
5kVA/ 6kVA: 200Vdc breaker or 200Vdc fuse is suggested.
2) 10kVA: 250Vdc breaker or 250Vdc fuse is suggested.
NOTE: Please contact your local dealer or customer service for external battery pack
connection and replacement.
5kVA/ 6kVA Level 1 Level 2 Level 3 Level 4
Total Battery Capacity 5~9Ah 9~17Ah 18~30Ah 27~40Ah
Charge Current 0.7A 1.4A 3A 4A
10kVA Level 1 Level 2 Level 3 Level 4
Total Battery Capacity 9~17Ah 13~20Ah 20~30Ah 27~40Ah
Charge Current 1.5A 2A 3A 4A