Delta 210 Series Specifications Page 1

Browse online or download Specifications for Water dispensers Delta 210 Series. Delta 210 Series Specifications User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 8
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Installation Instructions D- Series
Issue
Date October 6, 2003
D-70, D-140, D-210, and D-280 Series
Electric Non-Spring Return Actuators
(8, 16, 24, and 32 N·m)
Installation
Mount D- Series actuators in any convenient
orientation.
Install the actuators on a 3/8 to 3/4 in.
(9.5
to 19 mm) round shaft or a 3/8 to 5/8 in.
(9.5
to 16 mm) square shaft, 2 in. (51 mm) or longer. If
the
shaft is less than 2 in. (51 mm) long, install an
extension
recommended by the damper or valve
manufacturer.
IMPO
RTANT: The D- Series actuators are
intended to control equipment under normal
operating conditions. Where failure or malfunction of
a D- Series actuator could lead to an abnormal
operating condition that could cause personal injury
or damage to the equipment or other property, other
devices (limit or safety controls) or systems (alarm
or supervisory) intended to warn of, or protect
against, failure or malfunction of the D- Series
actuator must be incorporated into and maintained
as part of the control system.
To
mount the actuator, proceed as follows:
1. Press
and hold the gear release lever, and rotate
the
coupler to the 0 or 90° position. Release the
gear
release lever. (See Figure 1.)
Parts Included
Note: is the distance from the center of the
holes in the anti-rotation bracket to the center
of the shaft. (See Table 1 for dimensions.)
A
U-bolt
wi
th
Cl
amp
Nuts (2)
Shaft Center
Coupler
Gear
Release
Anti-rotation
Bracket
A
3
0
9
0
0
6
0
0
3
0
6
0
9
0
All Models
Del
ta D- Series actuator
DD
A-160 anti-rotation bracket
two No. 12-24 x 1/2 in. self-tapping hex
washer-head
screws
D24-210
and D24-280
Include one DDA-105 pluggable 3-terminal block
D24-210-FB135
and D24-FB1K
Include two DDA-105 pluggable 3-terminal blocks
D24-210-A
and D24-280-A
Include three DDA-105 pluggable 3-terminal blocks
Figure
1: Mounting Positions
Special Tools Needed
Table
1: Shaft Sizes and Distances from the
Anti-Rotation
Bracket to Shaft Center
torque wrench with 10 mm socket
digital
voltmeter or DDA-200 commissioning tool
(for the models with zero and span
po
tentiometers)
Shaft
Diameter 5/8 in. 1/2 in. 3/8 in.
A Dimensions
(See
F igure 1.)
6-1/8
in. 6-3/16 in. 6-1/4 in.
155 mm 157 mm 159 mm
Mounting
IMPORTANT: The actuator is intended for
indoor mounting only, with no direct exposure to
water beyond NEMA 2 conditions. Use an
appropriate shield or enclosure where the
environment exceeds NEMA 2 specifications.
2. Bend or cut the anti-rotation bracket to fit the
damper
frame or duct as shown in Figure 2.
© 2003 Delta Control Products, Inc. 1
Part No. 34-636-836, Rev F www.deltacp.com
Page view 0
1 2 3 4 5 6 7 8

Summary of Contents

Page 1 - Mounting

Installation Instructions D- Series Issue Date October 6, 2003 D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators (8, 16, 24,

Page 2

No. 12-24 SheetMetal Screws (2)Slot for BracketAnti-rotation BracketDamperFrameAnti-rotationBracket TabCover Screw 9. Press and hold the gear release

Page 3 - Rotation Range

Feedback Signal For resistance-type feedback, the signal varies with a change to the rotation range. Resistance feedback reduction corresponds to the

Page 4 - (Conduit Openings)

Through the Conduit Openings Depending on the D- Series model selected, use one or both conduit openings. The threaded actuator conduit openings acce

Page 5 - Setup and Adjustments

3. Connect the input control signal: • Terminal 102 from the master actuator to Terminal 102 on the slave actuator • For D24-210 and -280 models, c

Page 6

On/Off and Floating (D24) Models To set one of these models for RA operation, reverse the control wiring connections at Terminal 2 and Terminal 3. (Se

Page 7 - Technical Specifications

4. Retighten the Phillips-head screw on Switch S1, while holding it in the designated position. Switch S1 To change the angle of Switch S1 to 20°, re

Page 8

Technical Specifications (Cont.) Input Impedance DM24: Voltage Input 205,000 ohms for 0 (2) to 10 V and 410,000 ohms for 0 (4) to 20 V Current