Delta 210 Series Specifications Page 5

  • Download
  • Add to my manuals
  • Print
  • Page
    / 8
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 4
3. Connect the input control signal:
Terminal 102 from the master actuator to
Terminal 102 on the slave actuator
For D24-210 and -280 models, connect the input
control signal to the common, CW, and CCW
terminals on both the master and slave actuators.
(See Figure 7).
Terminal 103 from the master actuator to
Terminal 103 on the slave actuator
b. When mounting two actuators back-to-back on
the same shaft, connect:
For DM24-140, -210, and -280 Models, connect
the control signal to the master actuator and
connect 24 VAC/VDC power to both the master
and slave actuators.
Terminal 101 from the master actuator to
Terminal 102 on the slave actuator
Terminal 102 from the master actuator to
Terminal 101 on the slave actuator
IMPORTANT: For proper tandem operation,
do not connect the control input to the slave unit.
Note:
Terminal 103 from the master actuator to
Terminal 103 on the slave actuator
Set the master actuator jumpers on the
DM24-140, -210, and -280 models according to the
action and signal range desired before proceeding.
(Refer to Figure 8 and the Setup and Adjustments,
Calibration section.)
Note: The total wire length for these connections
may be up to 30 ft (9 m).
Span Potentiometer
Zero Potentiometer
Adjustable
Fixed
Jumper W3*
Factory Set
* -Z or -Z-A Models Only
Jumper W2
Factory Set
Voltage Input
0-10 VDC
Feedback Ouput
0 to 20 mA 4 to 20 mA
2-10 VDC
Current Input
Term i na l
Block 1
101 102 103
Jumper W1
Direct Acting (DA)
Reverse Acting (RA)
Rotation Direction with
Increasing Signal
Factory Set
(CCW) RA
(CW) DA
1 Common
2 Power
3 Calibration Ouput
(-Z or -Z-A Models Only)
4 Current Input
5 Voltage Input
6 Feedback Output
Note:
Jumpers W1, W2, W3, and W4
have no effect when the actuator
is in the Slave mode.
Master/Slave Jumper
(Shown in the
Master position)
Auxiliary Switches
(See Figure 5.)
Terminal
Block 1
Factory Set
Voltage Input
Jumper W4
Feedback Output
1 2 3 4 5 6
Note:
For current input,
Jumper W4 must
be in the 0 to 10 VDC
position.
101 102
103
4. Make sure of the following if the actuators
configured for tandem operation stall or do not
drive:
Both actuators have the same torque and
control input.
One actuator is set as the master and the
other as the slave.
The control signal is connected to the master
actuator only.
Terminal 101, Terminal 102, and Terminal 103
are connected properly, as described in
Step 2.
Setup and Adjustments
Calibration
Calibrate only the actuator designated as the master
when using a combination of two D24-210 or -280 or
two DM24-140, -210, or -280 models in tandem.
Direction of Action
In the DA mode, a minimum control signal drives the
actuator to the full CCW position, and a maximum
control signal drives it fully CW. In the RA mode, a
minimum control signal drives the actuator to the full
CW position, and a maximum control signal drives it
fully CCW. To set an actuator for RA, proceed to the
section for the appropriate model.
IMPORTANT: Adjust the rotation range before
changing the direction of action.
Figure 8: Settings on Proportional (DM24) Models
D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators Installation Instructions 5
Page view 4
1 2 3 4 5 6 7 8

Comments to this Manuals

No comments