DVP201/202/211LC-SL Load Cell Module Operation Manual
4-4
CR# Address Attribute Register name Explanation
CR#41: If the value in CR#41 is H’5678, all setting values will be stored in the flash memory. After the setting
values are stored, the value in CR#41 will become H’FFFF. If the value written to CR#41 is not H’5678, it will
automatically become H’0. For example, if H1 is written to CR#41, it will become H1. (After the adjustment of
points is complete, please use CR#41 to make adjustment parameters retentive.)
#42 H102A X R/W
Restoring all settings to
factory settings
Restoring all settings to factory settings (H’55AA)
#43 H102B X R/W
Way in which weights
measured by CH1 are
filtered out
#44 H102C X R/W
Way in which weights
measured by CH2 are
filtered out
K0: Not filtering weights (factory setting)
K1: Filtering out the maximum weight measured
K2: Averaging weights
#45 H102D X R/W Filter parameter for CH1
#46 H102E X R/W Filter parameter for CH1
Filtering out the maximum weight measured: K0~K8
Averaging weights: The number of weights which
need to be averaged should be in the range of K1 to
K100.
#48 H1030 O R/W
Range for determining
whether the digital value
corresponding to a weight
measured by CH1 is 0
grams
#49 H1031 O R/W
Range for determining
whether the digital value
corresponding to a weight
measured by CH2 is 0
grams
If the digital value corresponding to a weight
measured by CH1/CH2 is in the range specified, bit
5/bit 10 in CR#51 will be set (the weight measured
is will be counted as 0 grams).
Default value: K10
Setting range: K0~K32767
#51 H1033 X R/W Status code
The status of the load cell module used is stored in
this register. Please refer to the status table below
for more information.
Factory setting: H’0000
#52 H1034 O R/W RS-232 station address
#53 H1035 O R/W
RS-232 communication
format
#54 H1036 O R/W RS-485 station address
#55 H1037 O R/W
RS-485 communication
format
The default value in CR#52/CR#54 is K1. The
setting values in CR#52 and CR#54 should be in
the range of K1 to K255. The default value in
CR#53/CR#55 is H’0000 (ASCII, 9600 bps, 7 data
bits, even parity bit, one stop bit). Please refer to the
communication format table below for more
information.
#100 H1064 X R/W Current output Setting range: K0~K4000
#101 H1065 X R Digital input terminal Bit 0: X0; Bit 1: X1
#102 H1066 X R/W Digital output terminal Bit 0: Y0; Bit 1: Y1; Bit 2: Y2; Bit 3: Y3
#103 H1067 O R/W Way of outputting a current
K0: Digital value corresponding to a current output
in the range of 0 mA to 20 mA (factory setting)
K1: Digital value corresponding to a current output
in the range of 4 mA to 20mA
K2: Weight corresponding to a current output in the
range of 0 mA to 20mA
K3: Weight corresponding to a current output in the
range of 4 mA to 20mA