DVP201/202/211LC-SL Load Cell Module Operation Manual
4.3.5 Correspondence between Current Outputs and Weights
Currents outputs directly correspond to weights. Currents vary with weights. Users can set a current output
mode by means of CR#103.
Digital value
(CR#100)
K4000
K0
20mA
(Mode
0)
0mA
Current output
Digital value
(CR#100)
K4000
K0
20mA
(Mode
1)
4mA
Current output
Weight
(CR#12/13)
Maximum weight
(CR#37/38)
K0
20mA
(Mode2)
0mA
Current output
K0
20mA
(Mode3)
4mA
Current output
Weight
(CR#12/13)
Maximum weight
(CR#37/38)
Example: 10 kg correspond to 20 mA.
20mA
0g
10kg
0mA
A load cell module is directly connected to the left side of a DVP series PLC. The instruction TO is used to set
parameters.
CR#103 is set to K2, and CR#37/CR#38 is set to K10000. Please see the WPLSoft program shown below.