VFD-B Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-14
Parameters
Explanation Settings
Factory
Setting
16: CF2
17: Base Block (b.b)
18: oL2
19: CFA
20: code
21: EF1 (External Emergency Stop)
22: PHL (Phase-Loss)
23: cEF (Preliminary count value attained, EF
active)
24:Lc (Low-current)
25:AnLEr (Analog feedback signal error)
06-11
Fourth Most Recent
Fault Record
26:PGErr (PG feedback signal error)
06-12
Low-Current Detection
Level
00100% (00: Disabled)
00
06-13
Low-Current Detection
Time
0.1~ 3600.0 Sec
10.0
00: Warn and keep operating
01: Warn and ramp to stop
02: Warn and coast to stop
06-14 Low-Current Treatment
03: Warn, after coast to stop, restart (delay
06-15 setting time)
00
06-15
Low-Current Detection
Restart Delay Time
1~600 Min.
10
220VDC300VDC*
06-16
User-Defined
Low-Voltage Detection
Level
0: Disabled
00
06-17
User-Defined
Low-Voltage Detection
Time
0.1~ 3600.0 Sec 0.5
06-18 Reserved
Page view 132