8
VFD-B Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-15
Group 7 Motor Parameters
Parameters Explanation Settings
Factory
Setting
07-00 Motor Rated Current 30 to 120% 100
07-01 Motor No-Load Current 01 to 90% 40
07-02
Torque Compensation
0.0 to 10.0 0.0
07-03 Slip Compensation 0.0 to 3.0 0.0
07-04 Number of Motor Poles 02 to 10 04
07-05 Motor Parameters Auto Tuning
00: Disable
01: Auto Tuning
R1
02: Auto Tuning
R1 + No-load Test
00
07-06 Motor Line-to-line Resistance R1
0065535 mΩ
00
07-07 Reserved
07-08 Motor Rated Slip 0.00 to 20.00 Hz 3.00
07-09 Slip Compensation Limit 0 to 250% 200
07-10 Reserved
07-11 Reserved
07-12 Torque Compensation Time Constant 0.01 ~10.00 Sec
0.05
07-13 Slip Compensation Time Constant
0.05 ~10.00 Sec
0.10
07-14 Accumulative Motor Operation Time (Min.)
00 to 1439 Min.
00
07-15 Accumulative Motor Operation Day
00 to 65535 Day
00