Group 11 Fan & Pump Control Parameters
Parameters Explanation Settings
Factory
Setting
00: V/F Curve determined by
Pr.01-00 to Pr.01-06
01: 1.5 Power Curve
02: 1.7 Power Curve
03: Square Curve
11-00 V/F Curve Selection
04: Cube Curve
00
11-01
Start-Up Frequency of the
Auxiliary Motor
0.00 to 120.00 Hz 0.00
11-02
Stop Frequency of Auxiliary
Motor
0.00 to 120.00 Hz 0.00
11-03
Time Delay before Starting the
Auxiliary Motor
0.0 to 3600.0 sec 0.0
11-04
Time Delay before Stopping the
Auxiliary Motor
0.0 to 3600.0 sec 0.0
11-05 Sleep/Wake Up Detection Time 0.0 ~6550.0 sec 0.0
11-06 Sleep Frequency 0.00~Fmax 0.00
11-07 Wakeup Frequency 0.00~Fmax 0.00