When enabled, the AC drive will not start when powered up with run commands applied.
To start in Line Start Lockout mode, the AC drive must see the run command go from stop
to run after power up. When Line Start Lockout is disable (also known as Auto-Start), the
drive will start when powered-up with run commands applied.
The Line Start Lockout feature does not guarantee the motor will never start under this
condition. It is possible the motor may be set in motion by a malfunctioning switch.
02- 07
Loss of ACI Signal (4-20mA) Factory Setting: 00
Settings 00 Decelerate to 0Hz.
01 Stop immediately and display “EF”.
02 Continue operation by the last frequency command.
This parameter determintes the process when ACI is lost.
02 - 08
Up/Down Key Mode
a
Factory Setting: 00
Settings 00 Based on Accel/Decel Time
01 Constant speed
02 - 09
The Acce/Decel Speed of the UP/DOWN Key with
Constant Speed
a
Factory Setting: 0.01
Settings 0.01~1.00 Hz/msec
These parameters determine increasment/decreasment method of frequency command
when the Multi-Function Input parameters Pr.04-04~Pr.04-09 are set to 11 (Up command)
or 12 (Down command).
Pr.02-08=0: It will increase/decrease frequency command by the setting of accel/decel
speed.
Pr.02-08=1: It will accel/decel frequency command by Pr.02-09.
02 - 10
Source of the Master Frequency Command (FCHA)
a
Factory Setting: 00
Settings 00 Digital keypad
01 0 to +10V from AVI
02 4 to 20mA from ACI
03 -10 to +10Vdc from AUI
04 RS-485 communication interface