VFD-B Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-16
02 - 11
Source of the Auxiliary Frequency Command (FCHB)
a
Factory Setting: 00
Settings 00 Digital keypad
01 0 to +10V from AVI
02 4 to 20mA from ACI
03 -10 to +10Vdc from AUI
04 RS-485 communication interface
02 - 12
Combination of the Master and Auxiliary Frequency
Command
a
Factory Setting: 00
Settings 00 Master frequency + Auxiliary frequency
01 Master frequency - Auxiliary frequency
These three parameters (Pr.02-10~02-12) are enabled when Pr.02-00 or Pr.02-13 is set to
06. If they are enabled, the frequency command will be determined by these parameters.
02 - 15
Keyboard Frequency Command
a
Factory Setting: 60.00
Settings 0.00 ~ 400.00Hz Unit: 0.01
This parameter can be used to set frequency command or read keypad frequency
command.