VFD-B Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-27
Value Functions
Descriptions
06 Accel/Decel Inhibit
Parameter value 6 programs Multi-Function Input
Terminal: for Accel/Decel Inhibit. When the command
is active, acceleration and deceleration is stopped
and the AC drive maintains a constant speed.
07
Accel/Decel Time Selection
Command 1
08
Accel/Decel Time Selection
Command 2
Parameter value 7, 8 programs any two of
Multi-Function Input Terminals to select the one of
four Accel/Decel Time. (Pr.01-09 to Pr.01-12, Pr.01-18
to Pr.01-21)
09 External Base Block (NO)**
10 External Base Block (NC)***
Parameter values 9, 10 program Multi-Function Input
Terminals for external Base Block control. Value 9 is
for normally open (N.O.) input, and value d10 is for a
normally close (N.C.) input.
Note:
When a Base-Block signal is received, the AC drive
will stop all output and the motor will free run. When
base block control is deactivated, the AC drive will
start its speed search function and synchronize with
the motor speed, and then accelerate to Master
Frequency.
11 Increase Master Frequency
12 Decrease Master Frequency
Parameter values 11, 12 program the Multi-Function
Input Terminals to incrementally increase/ decrease
the Master Frequency each time an input is received.
Please refer to Pr.02-08, 02-09.
13 Counter Reset
Parameter value 13 programs Multi Function Input
Terminal to reset the counter.
14 Run PLC Program
15 Pause PLC Program
Parameter value 14 programs Multi-Function Input
Terminal to enable the AC drive internal PLC
program. Parameter value d15 programs an input
terminal to pause the PLC program.
Note: Pr.05-00 to Pr.05-16 defines the PLC program.
16
Auxiliary Motor No.1 output
failure
17
Auxiliary Motor No.2 output
failure
18
Auxiliary Motor No.3 output
failure
Parameter value 16 to 18 program Multi-Function
Input Terminal to disable the corresponding relay of
the AC drive multi-function output terminals, Pr.03-00
to 3-03 (MO1 to MO3).
19
Emergency Stop (NO)**
20 Emergency Stop (NC)***
Parameter value 19 to 20 program Multi-Function
Input Terminal to the AC drive to receive the signals of
malfunction and emergency stop. Please press
“RESET” after fault has been cleared.