VFD-B Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-42
17 External Base block stop (bb)
18 Motor over load (oL2)
19 Auto accel/decel failure (CFA)
20 Software/password protection (code)
21 Emergency stop (EF1)
22 PHL (Phase-Loss)
23 cEF (Preliminary count value attained, EF active)
24 Lc (Low-current)
25 AnLEr (Analog feedback signal error)
26 PGErr (PG feedback signal error)
Pr.06-08 to Pr.06-11 store records of the four most recent faults that had occurred. Use
the reset key to reset the drive when the fault no longer exits.
06 - 12
Low-Current Detection Level Factory Setting: 00
Settings 00 Disabled
00 ~ 100%
06 - 13
Low-Current Detection Time Factory Setting: 10.0
Settings 0.1~ 3600.0 Sec Unit: 0.1sec
06 - 14
Low-Current Treatment Factory Setting: 00
Settings 00 Warn and keep operating
01 Warn and ramp to stop
02 Warn and coast to stop
03 Warn, after coast to stop, restart (delay 06-15 setting time)
06 - 15
Low-Current Detection Restart Delay Time Factory Setting: 10.0
Settings 1~600.0 Min. Unit: 1min
If output current is lower than Pr.06-12 and exceed the time that Pr.06-13 sets during
running, AC drive will warn as Pr.06-14 sets. If Pr.06-14 is set to 03, AC drive will restart
after the delay time set by Pr.06-15 is up.