Delta PG-40 Specifications Page 81

  • Download
  • Add to my manuals
  • Print
  • Page
    / 179
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 80
VFD-B Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-46
07 - 09
Slip Compensation Limit
Factory Setting: 200
Settings 00 to 250% Unit: 1
This parameter can set the upper limit of the compensation frequency (the percentage
of Pr.07-08).
07 - 10
Reserved
07 - 11
Reserved
07 - 12
Torque Compensation Time Constant
Factory Setting: 0.05
Settings 0.01 ~10.00 Sec Unit: 0.01
07 - 13
Slip Compensation Time Constant
Factory Setting: 0.10
Settings 0.05 ~10.00 Sec Unit: 0.01
Setting the Pr.07-12 and Pr.07-13 can change the response time for the compensation.
07 - 14
Accumulative Motor Operation Time (Min.)
Factory Setting: 00
Settings 00 ~1439 Unit: 01
07 - 15
Accumulative Motor Operation Day
Factory Setting: 00
Settings 00 ~65535 Unit: 01
Pr.07-14 and Pr.07-15 are used to record the motor operation time. They can be cleared
by setting to 00 and won’t record if the time is less than 60 seconds.