Skip Frequency 1 Upper Bound
Factory Setting: 0.00
08 - 09
Skip Frequency 1 Lower Bound Factory Setting: 0.00
08 - 10
Skip Frequency 2 Upper Bound Factory Setting: 0.00
08 - 11
Skip Frequency 2 Lower Bound Factory Setting: 0.00
08 - 12
Skip Frequency 3 Upper Bound Factory Setting: 0.00
08 - 13
Skip Frequency 3 Lower Bound Factory Setting: 0.00
Settings 0.00 to 400.00Hz Unit: 0.01Hz
These parameters select the Skip Frequency. It will cause the AC drive to skip operation
at these frequency ranges with continuous frequency output.
Pr.08-09, Pr.08-11, Pr.08-13 are for Lower Bound setting, and the settings should follow
as Pr.08-09
Pr.08-11
Pr.08-13.
08 - 14
Auto Restart After Fault
Factory Setting: 00
Settings 00 to 10 Unit: 1
After fault occurs (allowable faults: over-current OC, over-voltage OV), the AC drive can
be reset/restarted automatically up to 10 times. Setting this parameter to 0 will disable
the reset/restart operation after any fault has occurred. When enabled, the AC drive will
restart with speed search, which starts at the Frequency before fault.
08 - 15
Automatic energy-saving
Factory Setting: 00
Settings 00 Energy-saving operation disabled
01 Energy-saving operation enabled