Delta PG-40 Specifications Page 87

  • Download
  • Add to my manuals
  • Print
  • Page
    / 179
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 86
VFD-B Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-52
Output frequency
(H)
Output voltage
(V)
FWD Run
B.B.
1
5
2
3
4
Fig 3: B.B. Speed Search with Minimum Output Frequency Upward Timing Chart
(
Start-up Current Attains Stall Current Level
)
A
Time
1
2
Stop output voltage
3
Disable B.B. signal
4
Waiting time 08-06
Restart
6
Stall prevention
5
06-01
Over current
stall prevention
during acceleration
6
7
7
Keep accelerating
08 - 19
Speed Search during Start-up
Factory Setting: 00
Settings 00 Speed search disable
01 Speed search enable
This parameter is used for starting and stopping a motor with high inertia. A motor with
high inertia will take a long time to stop completely. By setting this parameter, the user
does not need to wait for the motor to come to a complete stop before restarting the AC
drive. If a PG card and encoder is being used on the drive and motor, then the speed
search will start from the speed that is detected and accelerate quickly to the
commanded frequency. Pr.08-04 and Pr.08-06 will be disabled when using this
parameter with PG feedback control.
Note: Please make sure Pr.07-04, Pr.10-10, and Pr.10-11 are set correctly. An incorrect
setting may cause the motor to exceed its speed limit and permanent damage to the
motor and machine can occur.
08 - 20
Speed Search Frequency during Start-up
a
Factory Setting: 00
Settings 00 Setting Frequency
01 Maximum Operation Frequency (01-00)
This parameter determines the start frequency of speed search frequency.