VFD-B Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-54
Group 9: Communication Parameters
09 - 00
Communication Address
a
Factory Setting: 01
Settings 01 to 254
If the AC drive is controlled by RS-485 serial communication, the communication
address for this drive must be set via this parameter.
09 - 01
Transmission Speed
a
Factory Setting: 01
Settings 00 Baud rate 4800 (data transmission speed: bits / second)
01 Baud rate 9600 (data transmission speed: bits / second)
02 Baud rate 19200 (data transmission speed: bits / second)
03 Baud rate 38400 (data transmission speed: bits / second)
Users can set parameters and control the operation of the AC drive via the RS-485
serial interface of a personal computer. This parameter is used to set the transmission
speed between the computer and AC drive.
09 - 02
Transmission Fault Treatment
a
Factory Setting: 03
Settings 00 Warn and keep operating
01 Warn and RAMP to stop
02 Warn and COAST to stop
03 No warning and keep operating
This parameter is set to detect if an error occurs and take actions.
09 - 03
Time Out Detection
a
Factory Setting: 0.0
Settings 0.0 Disable
0.0 ~ 60.0 sec Unit: 1
If Pr09-03 is not equal to zero, Pr09-02=0~2, and there are not any communication on
the bus during setting time period (set by Pr. 09-03), “cE10” will be shown on the
keypad.
09 - 04
Communication Protocol
a
Factory Setting: 00
Settings 00 Modbus ASCII mode, protocol <7,N,2>
01 Modbus ASCII mode, protocol <7,E,1>
02 Modbus ASCII mode, protocol <7,O,1>
03 Modbus RTU mode, protocol <8,N,2>
04 Modbus RTU mode, protocol <8,E,1>
05 Modbus RTU mode, protocol <8,O,1>
Page view 88