Delta PG-40 Specifications Page 99

  • Download
  • Add to my manuals
  • Print
  • Page
    / 179
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 98
VFD-B Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-64
Content Address Function
14: Low voltage (Lv)
15: CPU failure 1 (cF1)
16: CPU failure 2 (cF2)
17: Base Block
18: Overload (oL2)
19: Auto accel/decel failure (cFA)
20: Software protection enabled (codE)
21: EF1 Emergency stop
22:PHL (Phase-Loss)
23:cEF (Preliminary count value attained, EF active)
24:Lc (Low-current)
25:AnLEr (Analog feedback signal error)
26:PGErr (PG feedback signal error)
Status of AC drive
LED: 0: light off, 1: light up
00: RUN LED
01: STOP LED
02: JOG LED
03: FWD LED
2101H
Bit 0-4
04: REV LED
Bit 5 0: F light off, 1: F light on
Bit 6 0: H light off, 1: H light on
Bit 7 0: “u” light off, 1: “u” light on
Bit 8
1: Main freq. Controlled by communication
interface
Bit 9 1: Main freq. controlled by analog signal
Bit 10
1: Operation command controlled by
communication interface
Bit 11 1: Parameters have been locked
Bit 12 0: AC drive stops, 1: AC drive operates
Bit 13 1: Jog command
Bit 14-15 Reserved
2102H Frequency command (F)
2103H Output frequency (H)
2104H Output current (AXXX.X)
2105H DC-BUS Voltage U (XXX.X)
2106H Output voltage E (XXX.X)
2107H Step number of Multi-Step Speed Operation
2108H Step number of PLC operation
2109H Content of external TRIGGER
210AH Power factor angle
210BH Estimated torque ratio
210CH Motor speed (Hz)
Page view 98
1 2 ... 94 95 96 97 98 99 100 101 102 103 104 ... 178 179