DELTA LTL-X Retrometer 37
OTHER SETTINGS
Average function
An average function can be activated showing the average of the measured Rl value calculat-
ed over a selectable number of measurements (2 to 25). The average mode can be fixed or
moving. In moving mode the average is always calculated from the last N measurements
where N is the selected number of measurements. In fixed mode the averaging will start over
again when N measurements have been taken. The average data is shown in the HOME
screen at the lower right corner (see picture pg. 17).
The average value is not stored in memory.
Press the MENU button and select AVERAGE:
AVERAGE OK
AVERAGE: ON
TYPE: MOVING
NUMBER: 10
RESET
AVERAGE:
Use the UP or DOWN button to highlight the first line. Press the OK button to toggle be-
tween AVERAGE ON and AVERAGE OFF.
TYPE:
Highlight the second line and press the OK button to toggle between type: MOVING
and type: FIXED.
NUMBER:
Highlight the third line and press the OK button to focus on the NUMBER digits. Then
use the UP or DOWN button to change the value between 2 and 25. Finally press the OK
button to confirm the new value (or you can amend changes by pressing LEFT or BACK).
The default setting is 4.
RESET:
Highlight the fourth line and press the OK button to reset the calculated average value
and reset the number of measurements included in the average to zero.