3-phase 2-phase L-L 1-phase L-N
Voltage Factor Voltage Factor
x 1.00 x 0.87 x 1.30
380v X 1.00 416v X 1.00
x 1.00 x 1.80 x 3.20
400v X 1.07 440v X 1.06
x 1.00 x 1.50 x 2.50
415v X 1.12 460v X 1.12
10 sec. 5 sec. 2 sec.
440v X 1.18 480v X 1.17
UCI224D
50Hz 60Hz
The sustained current value is constant irrespective
of voltage level
Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed
Based on star (wye) connection.
Max. sustained duration
All other times are unchanged
Instantaneous
Sustained
Minimum
Sustained Short Circuit = 230 Amps
Sustained Short Circuit = 275 Amps
Note 1
The following multiplication factors should be
used to adjust the values from curve between
time 0.001 seconds and the minimum current
point in respect of nominal operating voltage :
Note 2
The following multiplication factor should be used to convert the
values calculated in accordance with NOTE 1 to those applicable
to the various types of short circuit :
Note 3
Curves are drawn for Star (Wye) connected machines. For other
connection the following multipliers should be applied to current
values as shown :
Parallel Star = Curve current value X 2
Series Delta = Curve current value X 1.732
50
Hz
60
Hz
10
100
1000
10000
0.001 0.01 0.1 1 10
TIME (secs)
CURRENT (Amps)
SYMME TRICAL
ASYMMETRICAL
10
100
1000
10000
0.001 0.01 0.1 1 10
TIME (secs)
CURRENT (Amps)