Delta PG-45 User Manual Page 16

  • Download
  • Add to my manuals
  • Print
  • Page
    / 18
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 15
Features
3 phase AMF function*
Over/Under frequency
Over/Under voltage
Voltage asymmetry
3 phase generator protections
Over/Under frequency
Over/Under voltage
Current/Voltage asymmetry
Overcurrent/Overload
True RMS Voltage measurement
3 phase generator and mains* voltages
Voltage range 277 V p-n, 480 V p-p
Maximal measured voltage 300 V p-n
PT ratio range 0.1–500
True RMS current measurements
3 generator phase currents
Current range 5 A
Maximal measured current 10 A
CT ratio range 1–5000
Power measurements
Act / React Power and Power
Factor per phase
Active and Reactive Energy counter
InteliLite
NT
Event and performance log + RTC
Event based history with 119 events*
Reason, Data and Time + all
important values are stored
Battery backed-up RTC
Test Run scheduler
User interface
Graphic 128 × 64 pixels display
Multiple language capability
Setpoints adjustable via keyboard or PC
Buttons with mechanical feedback
Inputs and outputs
3 configurable analog inputs
6 or 7* Binary inputs
6 or 7* Binary outputs
Magnetic pick-up input
D+ preexcitation terminal
Optional 8 analog gauge drive outputs,
compatible with VDO, Datcon gauges
EFI engine support
Cummins MODBUS
Engine specific J1939 for all
major manufacturers
Diagnostic messages in plain text
Communication interfaces
Optional USB and RS232 plug-in modules
MODBUS RTU (requires RS232 module)
Internet
Mechanical and operation parameters
Unit dimension 120 × 180 mm
Sealed front face rated for IP65
Hard plexiglass LCD cover
Operation temperature
-20°C – +70°C standard version
-40°C – +70°C low temperature version
Power supply voltage 8–36 V
Voltage drops shorter than 50 ms
do not affect operation
Extension modules
IL-NT RS232 RS232 plug-in interface
IL-NT USB USB plug-in interface
IL-NT AOUT8 gauge plug-in interface
IL-NT RD remote display
IG-IB Internet module
IGS-PTM** extension I/O module
IGS-IOM** extension I/O module
IGL-RA15** 15 LED remote annunciator
* Only for Models AMF 20 and AMF 25
** Only for Models MRS 15, MRS 16 and AMF 25
IG-IB
PC
MODEM
+24V
IL-NT RD
or
or
STOP
ALARM
or
GENERATOR
DIESEL/GAS ENGINE
1
ENGINE
ANALOG
INPUTS
IL-NT
POWER SUPPLY
8 to 36 VDC
+
-
BINARY INPUTS
6x MRS xx
7x AMF xx
BINARY OUTPUTS
(OPEN COLLECTOR)
4x MRS xx
5x AMF xx
RS 232
INTERFACE
PLUG IN MODULE
BINARY
OUTPUTS
(OPEN
COLLECTOR)
D+
Oil Pressure
RPM
J1939
1
1
ECU
Start/Stop - Speed Request
Values + Fault Codes
Aux Alternator
Preexcitation
Fuel Solenoid
Starter
2
GENERATOR
CURRENT
VOLTAGE
MEASUREMENT
3
8 GAUGE DRIVERS
PLUG IN MODULE
IGL-RA15
IGS-PTM
IG-IOM
or
CAN - J1939
I/O EXTENS
ION
1
°C
LOAD
3ph
3ph
GENERATOR C.B. CONTROL
MAINS C.B. CONTROL
3ph
MAINS
MAINS
VOLT
AGE
MEASUREMENT
2
3
2
1
only on Models MRS15, MRS 16 and
AMF 25
only on Models AMF 20 and AMF 25
not on Models MRS 10 and MRS 15