17
Easy maintenance
The easily accessible components in the cen-
tral inverter cabinet make maintenance very
easy. If a fault should occur, the diagnostic
function will help you identify the affected module quickly
and allow a rapid replacement.
Technical data SOLIVIA CL 250 AP G1 MS
INPUT (DC)
Maximum recommended PV power 275 kW
P
Maximum voltage 850 V
Full power MPP range 450 ... 850 V
Max. current 573 A
OUTPUT (AC)
Max. power
1)
250 kW
Nominal power 250 kW
Nominal voltage 3 phase 290 V
Nominal frequency 50 / 60 Hz
Power factor (cos φ)
2)
≥ 0.99 @ nominal power
Total harmonic distortion (THD) < 3 % @ nominal power
GENERAL SPECIFICATION
Model names
4)
SOLIVIA CL 250 AP G1 MS (master)
SOLIVIA CL 250 AP G1 SL (slave)
Part numbers Delta
EOE98030414 (master)
EOE98030415 (slave)
Max. efficiency
5)
> 98.0 %
Efficiency EU
5)
> 97.5 %
Operating temperature -10 ... +40 °C
Storage temperature -25 ... +70 °C
Humidity 15 ... 85 % RH
Max. operating altitude 2000 m (above sea level)
MECHANICAL DESIGN
Size (L x W x D) 1800 x 1000 x 800 mm
Weight 600 kg
Cooling
Water cooling (closed loop system) / air cooling
(1100 m
3
/h)
AC connector Terminal clamps
DC connector Cable ring lugs
Communication
Ethernet, Internal PLC with data logger,
GPRS Modem (optional)
Display 15” Touch screen
STANDARDS / DIRECTIVES
Protection degree
3)
IP00
Safety class 1
Configurable trip parameters Yes
Insulation monitoring Yes
Anti-islanding protection Yes
EMC EN61000-6-2; EN61000-6-4
Safety EN50178; EN60439-1; EN50274
1) The maximum AC power value indicates the power an inverter might be able to deliver.
However, such a maximum AC power may not necessarily be achieved
2) Default; adjustable (-0.85 lagging to +0.85 leading)
3) IP00 with collar for exhaust air system. Depending on the connection of the exhaust air
system to the collar, a higher protection class is achieved
4) The CL 250 slave inverter lacks the HMI and PLC controller. The CL 250 master shows
the operating status of the complete system. A system consists of 1 master and up to 3
slaves
5) Ef ciency measured without transformer
Flexible system design to 1 MW
The SOLIVIA CL 250 inverter can be paralel-
led with up to 3 slave CL 250 inverters to allow
from 500 kW to 1 MW system designs.
Advanced utility capabilities
Adjustable cosPhi (-0.85 lagging to +0.85
leading), power reduction, VAR control, har-
monic correction.
User confi gurable interfaces
4 analog inputs, 13 digital inputs and 3 digital
outputs can all be con gured by the user for
various weather stations, temperature meas-
urements, and irradiation sensors.