Delta DTE10T Series User Manual Page 15

  • Download
  • Add to my manuals
  • Print
  • Page
    / 34
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 14
5GE1J?2'H


.=A2
(FUNCTION AND SPECIFICATION)

Power Supply DC24V. Isolated switching power supply
Voltage Range Rated voltage: 90%~110%
Power consumption Max. 10 W + 3 W x no. of DTC-2000 connected in parallel (max. 7)
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
Sensor Type
Platinum RTD: Pt100, JPt100, Cu50
Sampling Rate Thermocouple or Platinum RTD: 1.0 sec/all input.
Control Method PID , PID program control, Manual or ON/OFF
Relay output (SPST), Max. load 250VAC, 3A resistive load
Voltage pulse output: DC 24V, Max. output current 40mA
Current output: DC 4 ~ 20mA output (Resistive load < 500); for OUT1
and OUT2 only
Output accessories
(optional)
Analog voltage output: 0~10V (Resistive load > 1000); for OUT1 and
OUT2 only
Output Functions
Control output, alarm output or proportional output (proportional output is
only applicable in the model with linear voltage and current output for
OUT1, OUT2)
Alarm Modes 12 Alarm modes available
Communication RS-485 digital communication, Supports baud rate 2,400 ~ 115,200 bps.
Communication Protocol
Supports Mod-bus RTU/ASCII.
Extension port
The extension port transmits 24V power supply and communication
signals to extension module DTC2000.
Vibration Resistance 10 to 55Hz, 10m/s
2
for 10min, each in X, Y and Z directions
Shock Resistance Max. 300m/s
2
, 3 times each, 3 axes, 6 directions
Ambient Temperature
0
o
C to +50
o
C
Storage Temperature -20
o
C to +65
o
C
Altitude 2000m or less
Ambient Humidity 35% to 85% RH (non-condensing)
Pollution Degree Degree 2




Page view 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 33 34