With the Allen-Bradley driver installed, the “Advanced” tab under port properties will allow
selection of the configuration option for the port to act as a slave. This Allen-Bradley driver
does not support slave functionality, so this configuration option is not valid.
The Allen-Bradley driver supports PLC-5 Logical ASCII and binary addressing, and
SLC5/XX Protected Typed Logical addressing.
NOTE: When addressing registers, DeltaV PSIC register numbers are 1 based,
whereas PLC and SLC registers are 0 based.