50 Hz Mini/Micro
Computer Regulator (MCR) Series
Installation and Operation Manual
Contact Technical Services at (800) 377-4384 with any questions.
Fax-on-Demand: (877) 888-9329, Document #: 8412
13
Physical Characteristics of Operation – All Units
Operating Temperature
Standard units are designed to operate in ambient temperatures of -20
°
C
to +50
°
C. In operation, a temperature rise will occur whether or not the
transformer is serving a load. Normally, this rise may fall anywhere in the
range of 45-100
°
C. depending on the regulator type and rating. In any case,
the maximum operating temperature at an ambient of 50
°
C is always within
safe operating limits.
Magnetic Fields
In almost all applications, this effect may be disregarded. In certain
applications, care should be exercised in the orientation of the core with
respect to critical circuits, in order to minimize the effect in the field.
Electrical Characteristics of Operation – All Units
Checking with Voltmeters
All checks on output voltages should be made with a true RMS voltmeter.
Rectifier type voltmeters will not give accurate readings due to the small
amount of output harmonics present.
Load Regulation
Changes in output voltages resulting from changes in resistive loads from no
load to full load (at a 100% power factor) are approximately four percent.
Effect of Load Power Factor
The median value of output voltage will vary from the nameplate rating if the
load has a power factor other than that for which the regulator was designed.
Load regulation will also be greater as the inductive load power factor is
decreased. However, the resulting median values of output voltage will be
regulated against supply line changes at any reasonable load or load power
factor.