Chapter 4 Parameters| BLD-E1 Series
Revision May 2009, 00DE, V0.50 4-33
4.2 Description of Parameter Settings
Group 00 User Parameters
: This parameter can be set during operation.
00-00
Identity Code of the Brushless DC Motor Drive
Control
mode
VF VFPG FOCPM
Factory setting: Read Only
Settings Read Only
00-01
Rated Current Display of the Brushless DC Motor Drive
Control
mode
VF VFPG FCPM
Factory setting: Read Only
Settings Read Only
Pr. 00-00 determines the drive capacity that is set by the factory. It displays the identity code
of the brushless DC motor drive. The capacity, rated current, rated voltage and the max.
carrier frequency relate to the identity code. Users can use the following table to check how
the rated current, rated voltage and max. carrier frequency of the brushless DC drive
correspond to the identity code.
Pr.00-01 displays the rated current of the brushless DC motor drive. By reading this
parameter the user can check if it is correct for the brushless DC motor drive.
115V Series
460V Series
kW 0.2 0.4 0.75 0.4 0.75 1.5 2.2 3.7
HP 0.25 0.5 1.0 0.5 1.0 2.0 3.0 5.0
Pr.00-00
0 2 4 3 5 7 9 11
Rated Output
Current (A)
1.6 2.5 4.2 1.5 2.5 4.2 5.5 8.2
Max. Carrier
Frequency
15Hz
230V Series (1-phase) 230V Series (3-phase)
kW 0.2 0.4 0.75 1.5 2.2 0.2 0.4 0.75 1.5 2.2 3.7
HP 0.25 0.5 1.0 2.0 3.0 0.25 0.5 1.0 2.0 3.0 5.0
Pr.00-00
0 2 4 6 8 0 2 4 6 8 10
Rated Output
Current (A)
4.9 6.5 9.7 15.7 24 1.9 2.7 4.9 9.0 15 17.0
Max. Carrier
Frequency
15kHz
Page view 73