B Series Temperature Controller
User Manual
1 Precaution
DANGER! Caution! Electric Shock!
1. Do not touch the AC terminals while the power is supplied to the controller to prevent an electric shock.
2. Make sure power is disconnected while checking the unit inside.
3. The symbol indicates that this Delta B Series Temperature Controller is protected throughout by DOUBLE INSULATION or REINFORCED
INSULATION (equivalent to Class II of IEC 536).
WARNING!
This controller is an open-type temperature controller. Make sure to evaluate any dangerous application in which a serious human injury or serious
property damage may occur.
1. Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, width is 7.0mm (6.0mm for DTB 4824), hole diameter 3.2mm).
Screw size: M3 x 6.5 (With 6.8 x 6.8 square washer). Screw size for DTB4824: M3 x 4.5 (With 6.0 x 6.0 square washer). Recommended tightening
torque: 0.4 N.m (4kgf.cm). Applicable wire: Solid/twisted wire of 2 mm
2
, 12AWG to 24AWG. Please be sure to tighten them properly.
2. Do not allow dust or foreign objects to fall inside the controller to prevent it from malfunctioning.
3. Never modify or disassemble the controller.
4. Do not connect anything to the “No used” terminals.
5. Make sure all wires are connected to the correct polarity of terminals.
6. Do not install and/or use the controller in places subject to: (a) Dust or corrosive gases and liquid. (b) High humidity and high radiation. (c) Vibration and
shock. (d) High voltage and high frequency.
7. Must turn power off when wiring and changing a temperature sensor.
8. Be sure to use compensating wires that match the thermocouple types when extending or connecting the thermocouple wires.
9. Please use wires with resistance when extending or connecting a platinum resistance thermometer (RTD).
10. Please keep the wire as short as possible when wiring a platinum resistance thermometer (RTD) to the controller and please route power wires as far as
possible from load wires to prevent interference and induced noise.
11. This controller is an open-type unit and must be placed in an enclosure away from high temperature, humidity, dripping water, corrosive materials,
airborne dust and electric shock or vibration.
12. Make sure power cables and signals from instruments are all installed properly before energizing the controller, otherwise serious damage may occur.
13. Please do not touch the terminals in the controller or try to repair the controller when power is applied to prevent an electric shock.
14. Wait at least one minute after power is disconnected to allow capacitors to discharge, and please do not touch any internal circuit within this period.
15. Do not use acid or alkaline liquids for cleaning. Please use a soft, dry cloth to clean the controller.
16. This instrument is not furnished with a power switch or fuse. Therefore, if a fuse or power switch is required, install the protection close to the instrument.
Recommended fuse rating: Rated voltage 250 V, Rated current 1 A. Fuse type: Time-lag fuse
17. Note: This controller does not provide overcurrent protection. Use of this product requires that suitable overcurrent protection device(s) must be added to
ensure compliance with all relevant electrical standards and codes. (Rated 250 V, 15 Amps max). A suitable disconnecting device should be provided
near the controller in the end-use installation.
2 Display, LED and Pushbuttons
PV Display
SV Display
AT
OUT1/OUT2
Function key
Temperature unit LED
Down key
Up
: to display the process value or parameter type.
: to display the set point, parameter operation read value,
manipulated variable or set value of the parameter.
: flashes when the Auto-tuning operation is ON.
: Output LED ights when the output is ON.
: . Press this key to select the desired function mode and
confirm a setting value.
C, F : .
ALM1 ~ ALM3 : Alarm output LED, lights when ALM1/ALM2/ALM3 is ON.
: . Press this key to decrease values displayed on the SV
display. Hold down this key to speed up the decrements.
:
O
Auto-tuning LED,
, l
: . Press this key to set parameters within function mode.
C : Celsius F : Fahrenheit
. Press this key to increase values displayed on the SV display.
Hold down this key to speed up the incremental action.
Mode key
key
OOO
3 Ordering Information
DTB
1 2 3 4 5 6 7
DTB Series DTB : Delta B Series Temperature Controller
1 2 3 4
Panel Size (W×H)
4824: 1/32 DIN W48 x H24mm; 4848: 1/16 DIN W48 x H48mm;
4896: 1/8 DIN W48 x H96mm; 9696: 1/4 DIN W96 x H96mm
5
1st Output Group Selection
R: Relay output, SPDT (SPST: 1/16 DIN and 1/32 DIN size), 250VAC, 5A
V: Voltage pulse output, 14V +10%~ -20% (Max. 40mA)
C: DC current output, 4 ~ 20m A; L: Linear voltage output, 0~5V, 0~10Vdc
6
2nd Output Group Selection
R: Relay output, SPDT (SPST: 1/16 DIN and 1/32 DIN size), 250VAC, 5A
V: Voltage pulse output, 14V +10%~ -20% (Max. 40mA)
7
EVENT Inputs /
CT function (Optional)
None: No EVENT input, No CT (Current transformer); E: EVENT input is provided, No CT (Current transformer)
T: CT (Current transformer) is provided, No EVENT input; V: Valve control.
Note 1: DTB4824 series: no optional function provided and no extra alarm output supported, but user can set 2nd output as alarm mode.
Note 2: DTB4848 series: only one alarm output when optional function supported, but user can set 2nd output as 2nd alarm output.
Note 3: “Valve control” with feedback selection is only available for DTB9696RRV.