Setting MODBUS RS-485 communication for Delta products
Rev.: 00
Doc. Code:
134A-P-D1410-APN002-EN
Page 4/11
3. Methods of Setting a Product
The communication timeouts and the delay times set for Delta control products are different. They can be modified in the
ways shown in Table 2.
Table 2 Communication parameters in a MODBUS master station
Communication timeout Delay time
Model Software Program
Default
value
Software Program
Default
value
DOP series None 1000 None 0
AH500 series
SR210
SR213
3000 None SR1339 0
DVP series D1129
0
(Scan time)
None D1038
0
TP series None None 100 None None 0
IFD9506/7 None 5000 None 0
RTU-EN01 None 5000 None 0
The following sections introduce the modification of the communication timeouts and the delay times set for products by
means of software and programs.
3.1 AH500 Series
3.1.1 PLC
Users can set a communication timeout and a delay time for an AH500 series PLC by means of HWCONFIG in ISPSoft
or writing a program in ISPSoft.
(1) Setting a communication timeout by means of ISPSoft
Steps: Start HWCONFIG.Set the parameters in the PLC.Click the COM Port tab.Download the parameters to
an AH500 series PLC.
a. Start HWCONFIG in ISPSoft.