50 Hz Mini/Micro
Computer Regulator (MCR) Series
Installation and Operation Manual
Contact Technical Services at (800) 377-4384 with any questions.
Fax-on-Demand: (877) 888-9329, Document #: 8412
9
Other Considerations for Hardwired Units
Three Phase Operation
If operation from a three phase source is required, three hardwired regulators
may be wired in delta as shown in Figure 4.
Note
Required branch circuit protection must be located in the primary of each
regulator, not in the three phase line. The outputs must supply three
independent single phase loads of the same voltage rating. Do not connect
loads phase to phase when the three phase configuration is used.
Multiple Operation
Two or more hardwired models of the same rating may be connected with
their input and output in parallel. However, on models smaller than 5kVA,
do not parallel both 220VCT (X1-X2-X3) and 240VCT (X4-X2-X5). This may
damage the output windings.
Input Power Switch
Because the regulators include resonant circuitry that is energized whether
or not the unit is serving a load, it is very desirable to install a disconnect
switch in the primary circuit.