AH500 Hardware Manual
9-32
Error code Description Remedy
same as the length of the
PDO set in the node list.
16#A0E2
AH10COPM-5A does not
receive a PDO from a slave
station.
Make sure that the PDOs in the slave station are set correctly.
16#A0E3
An automatic SDO is not
downloaded successfully.
Make sure that the automatic SDO is et correctly.
16#A0E4
A PDO parameter is not set
successfully.
Make sure that the setting of the PDO parameter is legal.
16#A0E5
A key parameter is set
incorrectly.
Make sure that the slave stations connected are the same as
the slave stations set.
16#A0E6
The actual network
configuration is not the same
as the network configuration
set.
16#A0E7
The control of the errors in a
slave station is not sent after
a set period of time.
Make sure that the power supplied to the slave stations
connected is normal and the network created is connected
correctly.
16#A0E8
The master station address is
the same as a slave station
address.
Set the master station address or the slave station address
again, and make sure the new station address is not the
same as a slave station address.
16#A0F1
No slave station is added to
the node list in CANopen
builder.
Add slave stations to the node list, and download the
configuration to AH10COPM-5A.
16#A0F3
An error occurs in
AH10COPM-5A.
Download parameters again. If the error still occurs, please
replace AH10COPM-5A.
16#A0F4 The bus used is off.
Please check whether the bus cable on the CANopen
network created is connected correctly, make sure that the
serial transmission speeds of all the nodes on the network
are the same, and power AH10COPM-5A again.
16#A0F5
The node address of
AH10COPM-5A is set
incorrectly.
The node address of AH10COPM-5A must be in the range of
1 to 127.
16#A0F6
Internal error: An error occurs
in the manufacturing process
in the factory.
16#A0F7 Internal error: GPIO error
16#A0F8 Hardware error
Power AH10COPM-5A again. If the error still occurs, please
replace AH10COPM-5A.
16#A0F9 Low voltage
Make sure that the power supplied to AH10COPM-5A is
normal.
16#A0FA
An error occurs in the
firmware of AH10COPM-5A.
Power AH10COPM-5A again.
16#A0FB
The transmission registers in
AH10COPM-5A are full.
Please make sure that the bus cable on the CANopen
network created is connected correctly, and power
AH10COPM-5A again.
16#A0FC
The reception registers in
AH10COPM-5A are full.
Please make sure that the bus cable on the CANopen
network created is connected correctly, and power
AH10COPM-5A again.