Delta RMC101 User Manual Page 230

  • Download
  • Add to my manuals
  • Print
  • Page
    / 951
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 229
RMC100 and RMCWin User Manual
4-44
To scale the MDT position axis, the following steps are performed:
Click on any Axis 0 field.
On the Tools menu, click MDT Scale/Offset Calibration. The following window opens:
The position feedback is to be measured in thousandths of inches, so 1000 pos units per inch is
entered in the Desired Position Units field.
The transducer gradient information in the Transducer field is found on the transducer.
To set the offset, the following steps are performed
o Retract the cylinder all the way. This can be done by issuing an Open Loop (O) command
with a small amount of drive.
o When the cylinder is all the way retracted, the transducer shows 1024 counts in this
example.
o If this is the desired zero point, click the button in the Offset field and it automatically enters
Page view 229
1 2 ... 225 226 227 228 229 230 231 232 233 234 235 ... 950 951

Comments to this Manuals

No comments