RMC100 and RMCWin User Manual
5-216
3. If you are creating a new PROFIBUS-DP network, you must create a new network and add a
master device to the network.
On the File menu, click New. If you have multiple networks installed you will need to then select
the network type: select PROFIBUS. If you are not given the option of selecting PROFIBUS,
you may not have installed the PROFIBUS driver for SyCon.
On the Insert menu, click Master. Move the cursor to the top device slot in the window area (the
cursor will change to an arrow with an ’r;M’ next to it), and click to place the master device.
In the Insert Master dialog box, select the desired master and click the Add>> button. Enter the
station address, and click OK.
On the Settings menu, click Bus Parameter.
In the Bus Parameter dialog box, set the Baud Rate to the desired rate. The RMC is capable of
speeds up to 12000kBits/s (12MBaud); check the rates supported by your master and other
slaves. Click OK.
4. Add the DELT1630.GSD file to your configuration program’s GSD database.
You must first have an open PROFIBUS project file.
On the File menu, click Copy GSD.
In the Open dialog box, navigate to the directory where the DELT1630.GSD file is located (by
default it is installed in the main RMCWin directory), select that file and click Open.
NOTE: This will not add the bitmap file. If you wish to use the bitmap file; copy the
DELTRMCN.BMP file to the Fieldbus\Profibus\BMP directory under the SyCon directory (by
default, the total path will be C:\Program Files\Hilscher GmbH\SyCon\Fieldbus\Profibus\BMP).
5. Add a Delta RMC Family slave device to the network.
On the Insert menu, click Slave. Move the cursor to the next available device slot in the window
area (the cursor will change to an arrow with an S next to it), and click to place the device.
In the Insert Slave dialog box, click Delta RMC Family, and then click the Add>> button. Enter
the station address, and click OK.
6. Configure the RMC Slave Device. This involves selecting the correct configuration module for
your RMC module and application. Refer to the sub-topic Determining the Appropriate GSD
Configuration Module in the PROFIBUS Configuration topic for details on selecting the correct
configuration module.
Right-click on the RMC slave device icon, and click Slave Configuration from the shortcut
menu.
In the Slave Configuration dialog box, from the list of order numbers, select the configuration
module you selected in the previous steps.
Click Append Module.
You may change the I Addr. and O Addr. fields for the added module to set the offsets of the
data.
Click OK.