Delta PG-40 Specifications Page 107

  • Download
  • Add to my manuals
  • Print
  • Page
    / 179
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 106
VFD-B Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-72
FWD
CCW
REV
CW
PULSE
GENERATOR
PG
10-11=02
10-11=03
A
phase leads B phase
A phase
A phase
A phase
B phase
B phase
B phase
CW
B phase leads A phase
10 - 12
Proportional Speed Control (P) a
Factory Setting: 1.0
Settings 0.0 to 10.0 Unit: 0.1
This parameter specifies Proportional control and associated gain (P), used for vector
control with PG feedback.
Note: The parameter can be set during operation.
10 - 13
Integral Speed Control (I) a
Factory Setting: 1.00
Settings 0.00 to 100.00 Unit: 0.01
0.00 disable
This parameter specifies Integral control and associated gain (I), used for vector control
with PG feedback.
Note: The parameter can be set during operation.
10 - 14
Speed Control Output Frequency Limit
Factory Setting: 10.00
Settings 0.00 to 10.00 Unit: 0.01Hz
This parameter limits the amount of correction by the PI control on the output frequency
when controlling speed. It can limit the maximum output frequency.
10-13
I
P
10-12 10-14
+
-
+
+
+
Frequency Command
Speed Detection
Output Frequency
Output
Frequency
Limit
Speed Control Diagram
Page view 106