Delta PG-40 Specifications Page 78

  • Download
  • Add to my manuals
  • Print
  • Page
    / 179
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 77
5
VFD-B Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-43
06 - 16
User-Defined Low-Voltage Detection Level Factory Setting: 00
Settings 00 Disabled
230V series: 220 ~ 300VDC
460V series: 440 ~ 600VDC
06 - 17
User-Defined Low-Voltage Detection Time Factory Setting: 0.5
Settings 0.1~ 3600.0 Sec Unit: 0.1sec
When the voltage of DC BUS is lower than Pr.06-16 and the time exceeds the setting of
Pr.06-17, AC drive will output a signal by the setting 28 of Pr.03-00 ~ Pr.03-03.
06 - 18
Reserved