34 Operation and installation manual SOLIVIA 3.3 AP G3 TR
(In the eld, the rst step is to scan for potential fault causes that could be picked up by
the solar inverter and result in tripping.)
Various key parameters can be scanned via the display, thereby enabling conclusions
to be drawn about potential fault causes.
Current values in the N menu
AC Voltage -> Display of current output voltage -> Voltage limiting values
AC Frequency -> Display of current grid frequency -> Frequency limiting values
Solar Voltage -> Display of current PV cell voltage -> Switch-in threshold
9.2 Display messages
LED STATUS
DISPLAY
MESSAGE
CAUSE ELIMINATION
green: <on>
red: <on>
yellow: <on>
Display communication
faulty.
If the fault persists after the device
has been reset, please inform your
service technician.
green: <off>
red: <off>
yellow: <on>
AC frequency
failure
Grid frequency overshoo-
ting or undershooting
specied limit range.
Check the grid frequency via the
display in the N menu.
green: <off>
red: <off>
yellow: <on>
AC voltage
failure
Grid voltage overshooting
or undershooting specied
limit range.
Check the grid voltage via the
display in the N menu.
If no voltage present, check grid
automatic circuit breaker.
green: <off>
red: <off>
yellow: <on>
AC relay
failure
One of the anti-islanding
protection output relays is
faulty / defective.
The solar inverter is defective.
Return the device.
green: <ashes>
red: <off>
yellow: <off>
Calibration
ongoing
Check internal settings. Normal function before input mode.
green: <off>
red: <off>
yellow: <on>
DC injection
failure
DC component of input-
side alternating current is
too high.
If the fault persists after the device
has been reset, please inform your
service technician.
green: <off>
red: <off>
yellow: <on>
Error # 301
Internal communication
error or hardware fault.
If the fault persists after the device
has been reset, please inform your
service technician.
green: <off>
red: <off>
yellow: <on>
Error # 302
The device trips and
reverts to grid input mode
once the temperature has
dropped.
Check the installation site (no
direct sunlight, air circulation).
green: <off>
red: <on>
yellow: <off>
Error # 506
Error # 508
Isolation resistance fault
on the DC side during
start-up phase (# 508) or
running phase (# 506).
Check the isolation resistance on
the DC side of the PV modules.
green: <on>
red: <on>
yellow: <off>
Isolation
start-up
warning
Isolation run-
ning warning
Isolation resistance fault
on the DC side during
start-up phase or running
phase.
You must check the isolation
resistance on the DC side of the
PV modules. Solar inverter is still
feeding!