Setting MODBUS RS-485 communication for Delta products
Rev.: 00
Doc. Code:
134A-P-D1410-APN002-EN
Page 6/11
(2) Setting a communication timeout and a delay time by means of a program
a. Communication timeout: SR210Set SM209 (COM1).
(COM2: SR213Set SM211.)
b. Delay time: SR1339
Example: The communication timeout set for COM1 on a PLC is changed to ten milliseconds, and the delay time set
for the PLC is changed to five milliseconds.
Figure 1 Program written for an AH500 series PLC
3.1.2 Network Module
Users can set the RS-485 parameters in the serial communication module AH10SCM-5A by means of ISPSoft.
Steps: Start HWCONFIG.Set the parameters in AH10SCM-5A. Set COM 1.Download the parameters to
AH10SCM-5A.
a. Start HWCONFIG in ISPSoft.
b. Open the Parameter Setting window by double-clicking AH10SCM-5A.