12-1
TROUBLESHOOTING
SM DELTA 1-E.2 GB
12. TROUBLESHOOTING
WARNING!!!
When Power Up – the whole outdoor unit controller, including the wiring, is
under HIGH VOLTAGE!!!
Never open the Outdoor unit before turning off the Power!!!
When turned off, the system is still charged (400V)!!!
It takes about 4 Min. to discharge the system.
Touching the controller before discharging may cause an electrical shock!!!
12.1
Single Split system failures and corrective
actions
No SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION
1
Power supply indicator
(Red LED) does not light
up.
No power supply
Check power supply. If power supply
is OK, check display and display
wiring. if OK, replace controller.
2
Unit does not respond to
remote control message Remote control message
not reached the indoor
unit
Check remote control batteries, if
batteries are OK, check display and
display wiring, if OK, replace display
PCB.
If still not OK replace controller.
3
Unit responds to remote
control message but
Operate indicator (Green
LED) does not light up
Problem with display
PCB
Replace display PCB.
If still not OK replace controller.
Unit in heat mode and
coil is still not warm.
Change to cool mode and check.
4
Indoor fan does not start
(louvers are opened and
Green LED does light up)
Problem with PCB or
capacitor
Change to high speed and Check
power supply to motor is higher than
130VAC (for triack controlled motor)
or higher than 220VAC for fixed
speed motors, if OK replace
capacitor, if not replace controller
5
Indoor fan works when
unit is OFF, and indoor
fan speed is not changed
by remote control
command.
PCB problem
Replace controller
6
Compressor does not
start
Electronics control
problem or protection
Perform diagnostics , and follow the
actions described.
7
Compressor stops during
operation and Green
LED remains on
Electronic control or
power supply problem
Perform diagnostics ,and follow the
actions described.
8
Compressor is on but
outdoor fan does not
work
Problem with outdoor
electronics or outdoor fan
Check outdoor fan motor according
to the procedure in section, if not OK
replace controller