CONTROL SYSTEM
SM DELTAZ 1-E.0 GB
11.6 Dry Mode
As long as room temperature is higher then the set point, indoor fan will work in low speed and
compressor will work between 0 and MaxNLOADIF1C Hz.
When the room temperature is lower than the set point, compressor will be switched OFF and
indoor fan will cycle 3 minutes OFF, 1 minute ON.
11.7 Protections
There are 5 protection codes.
Normal (Norm) – unit operate normally.
Stop Rise (SR) – compressor frequency can not be raised but does not have to be decreased.
HzDown1 (D1) – Compressor frequency is reduced by Down1 Hz/min.
HzDown2 (D2) – Compressor frequency is reduced by Down2 Hz/min.
Stop Compressor (SC) – Compressor is stopped.
11.7.1 Indoor Coil Defrost Protection
ICT
ICT Trend
Fast
Increasing
Increasing No change Decreasing
Fast
Decreasing
ICT < -2 SC SC SC SC SC
-2 ICT < 0 D1 D1 D2 D2 D2
0 ICT < 2 SR SR D1 D2 D2
2 ICT < 4 SR SR SR D1 D2
4 ICT < 6 Norm Norm SR SR D1
6 ICT < 8 Norm Norm Norm SR SR
8 ICT Normal
11.7.2 Indoor Coil over Heating Protection
ICT
ICT Trend
Fast
Decreasing
Decreasing No Change Increasing
Fast
Increasing
ICT > 55 SC SC SC SC SC
53 < ICT 55 D1 D1 D2 D2 D2
49 < ICT 53 SR SR D1 D2 D2
47 < ICT 49 SR SR SR D1 D2
45 < ICT 47 Norm Norm SR SR D1
43 < ICT 45 Norm Norm Norm SR SR
ICT 43 Normal