12-1
TROUBLESHOOTING
SM DELTAZ 1-E.0 GB
12 TROUBLESHOOTING
12.1 ELECTRICAL & CONTROL TROUBLESHOOTING
WARNING!!!
When Power Up – the whole outdoor unit controller, including the wiring, is under HIGH
VOLTAGE!!!
Never open the Outdoor unit before turning off the Power!!!
When turned off, the system is still charged (400V)!!!
It takes about 4 Min. to discharge the system.
Touching the controller before discharging may cause an electrical shock!!!
For safe handling of the controller please refer to section 12.3 below.
12.1.1 Single Split system failures and corrective actions
No SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION
1
Power supply indicator (Red
LED) does not light up.
No power supply
Check power supply. If power supply is OK,
check display and display wiring. if OK,
replace controller.
2
Unit does not respond to
remote control message
Remote control
message not reached
the indoor unit
Check remote control batteries, if batteries
are OK, check display and display wiring, if
OK, replace display PCB.
If still not OK replace controller.
3
Unit responds to remote
control message but Operate
indicator (Green LED) does
not light up
Problem with display
PCB
Replace display PCB.
If still not OK replace controller.
4
Indoor fan does not start
(louvers are opened and
Green LED does light up)
Unit in heat mode and
coil is still not warm.
Change to cool mode and check.
Problem with PCB or
capacitor
Change to high speed and Check power
supply to motor is higher than 130VAC
(for triack controlled motor) or higher than
220VAC for fixed speed motors, if OK replace
capacitor, if not OK replace controller
5
Indoor fan works when unit is
OFF, and indoor fan speed is
not changed by remote control
command.
PCB problem Replace controller
6
Compressor does not start
Electronics control
problem or protection
Perform diagnostics (See 12.1.3 below), and
follow the actions described.
7
Compressor stops during
operation and Green LED
remains on
Electronic control or
power supply problem
Perform diagnostics (See 12.1.3 below), and
follow the actions described.
8
Compressor is on but outdoor
fan does not work
Problem with outdoor
electronics or outdoor
fan
Check outdoor fan motor according to the
procedure in section 12.2.3 below, if not OK
replace controller
9
Unit works in wrong mode
(cool instead of heat or heat
instead of cool)
Electronics or power
connection to RV
Check RV power connections, if OK,
Check RV operation with direct 230VAC
power supply, if OK,
Replace outdoor controller.
10
All components are operating
properly but no cooling or no
heating
Refrigerant leak Check refrigeration system.