PROFIBUS DP Slave Communicaion Module RTU-PD01
DVP-PLC Operation Manual
14
Definitions of configuration items:
Parameter Value Definition
Location 0 ~ 7
The location of DVP06XA-S at the right side of RTU-PD01. The
location of the first special I/O module at the right side of
RTU-PD01 is 0, the second is 1 and so forth. This rule is only
applicable on special I/O modules.
-10V ~ +10V
The input channel on DVP06XA-S is set to mode 0: Voltage input
mode. Input range: -10V ~ +10V
-6V ~ +10V
The input channel on DVP06XA-S is set to mode 1: Voltage input
mode. Input range: -6V ~ +10V
-12mA ~ +20mA
The input channel on DVP06XA-S is set to mode 2: Current input
mode. Input range: -12mA ~ +20mA
CH1 input mode
CH2 input mode
CH3 input mode
CH4 input mode
-20mA ~ +20mA
The input channel on DVP06XA-S is set to mode 3: Current input
mode. Input range: -20mA ~ +20mA
0V ~ 10V
The output channel on DVP06XA-S is set to mode 0: Voltage
output mode. Output range: 0V ~ +10V
2V ~ 10V
The output channel on DVP06XA-S is set to mode 1: Voltage
output mode. Output range: 2V ~ 10V
4mA ~ 20mA
The output channel on DVP06XA-S is set to mode 2: Current
output mode. Output range: 4mA ~ 20mA
CH5 output mode
CH6 output mode
0mA ~ 20mA
The output channel on DVP06XA-S is set to mode 3: Current
output mode. Output range: 0mA ~ 20mA
Current value Current value of the input signal in CH1 ~ CH4 on DVP06XA-S
Input value mode
Average value Average value of the input signals in CH1 ~ CH4 on DVP06XA-S
Set average times 1 ~ 4096 The average times