DVP-ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming
3-358
2. M1136M1138: retain communication setting
3. D1252D1249: Set value for data receiving timeout
4. M1320M1139: ASCII/RTU mode selection
5. M1316M1312: sending request
6. M1318M1314: receiving completed flag
H87
MOV
M1002
D1109
SET M1136
K100
MOV
D1252
MODRW K16K1
X0
H2000 D50 K2
Connection device address: K1
Function Code: K16
Write in multiple Word data
Data address: H2000
Datat register:
D50 = H1770, D51=H12
Data length: K2
SET
X0
M1316
RST
M1320
SET
M1320
M1320 = OFF
ASCII mode
Set communication protocol as 9600,8,E,1
Retain communication setting
Set communication timeout as 100ms
Sending request
M1320 = ON
RTU mode
RST M1318
M1318
Reset M1318
ASCII mode: No processing on received data .
RTU mode: No processing on received data .
Received data
Receiving completed
z ASCII mode (COM3: M1320 = OFF, COM1: M1139 = OFF):
When X0 = ON, MODRW executes the function specified by Function Code H10
PLC ÖVFD-B, PLC sends: “01 10 2000 0002 04 1770 0012 30”
VFDÖPLC, PLC receives: “01 10 2000 0002 CD”
(No processing on received data)
z RTU Mode (COM3: M1320=On, COM1: M1139=On):
When X0 = ON, MODRW executes the function specified by Function Code H10
PLC ÖVFD-B,PLC sends: 01 10 2000 0002 04 1770 0012 EE 0C”
VFD-BÖPLC, PLC receives :01 10 2000 0002 4A08
(No processing on received data)