Delta DVP-ES2 User Manual Page 236

  • Download
  • Add to my manuals
  • Print
  • Page
    / 702
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 235
DVP-ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming
3-120
API Mnemonic Operands Function
51
REFF P
Refresh and Filter Adjust
Controllers
ES2/EX2 SS2
SA2
SE
SX2
Bit Devices Word devices Program Steps Type
OP
X Y M S K H KnX KnY KnM KnS T C D E F
n
* *
REFF, REFFP: 3 steps
PULSE 16-bit 32-bit
ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2
Operands:
n: Response time (unit: ms)
Explanation:
1. PLC provides digital input filters to avoid interference. The response time (n) of X0 ~ X7 input
filters can be adjusted by REFF instruction. The instruction sets the value specified in n to
D1020 (X0 ~ X7 input filter time) directly.
2. When PLC turns from OFF to ON or the END instruction is reached, the response time is
dictated by the value of D1020.
3. During program execution, the value in D1020 can be changed by using MOV instruction.
4. When using REFF instruction during program execution, the modified response time will be
move to D1020 and refreshed until next program scan..
5. Range of n: = K2 ~ K20.
Program Example:
1. When the power of PLC turns from OFF to ON, the response time of X0~X7 inputs is
specified by the value in D1020.
2. When X20 = ON, REFF K5 instruction is executed, response time changes to 5 ms and takes
affect the next scan.
3. When X20 = OFF, the REFF instruction will not be executed, the response time changes to
20ms and takes affect the next scan.
X20
REFF K5
X0
Y1
X20
REFF K20
X1
Y2
END
Points to note:
Response time is ignored (no delay) when input points are occupied by external interrupts,
high-speed counters or SPD instruction.
Page view 235
1 2 ... 231 232 233 234 235 236 237 238 239 240 241 ... 701 702

Comments to this Manuals

No comments