3. Instruction Set
3-333
3. In ASCII or RTU mode, when PLC’s COM2 sends out data, the data will be stored in
D1256~D1295. The feedback data will be stored in registers starting with S and converted into
D1296~D1311 in Hex automatically.
4. Take the connection between PLC1 (PLC COM2) and PLC2(PLC COM1) for example, the
tables below explains the status when PLC1 reads Y0~Y17 of PLC2.
H87MOV
M1002
D1120
SET M1120
K100
MOV
D1129
RST M1127
Set communication protocol as 9600, 8, E, 1
Retain communication protocol
Set communication timeout as 100ms
MODRW
K2
K1
X0
H0500 D0 K16
Connection device
address K1
Function code K2
read multiple bits
Data address Y0=H0500
Data storing register
Data length (bit)
Processing received data
ASCII mode: The received data is stored in registers starting from D0 in ASCII format and
PLC converts the content to hexadecimal automatically.registers D1296~D1311 in
RTU mode: The received data is stored in registers starting from D0 in Hex.
Reset M1127
M1127
SET
X0
M1122
Sending request
M1143 = OFF
ASCII mode
RST
M1143
M1143 = ON
RTU mode
SET
M1143
Receiving completed
ASCII Mode (M1143 = OFF):
When X0 = ON, MODRW instruction executes the function specified by Function Code 02.
PLC1Ö PLC2PLC1 sends: “01 02 0500 0010 E8
PLC2 ÖPLC1PLC1 receives: “01 02 02 3412 B5
Registers for data to be sent (sending messages)
Register Data Descriptions
D1256 Low ‘0’ 30 H ADR 1
D1256 High ‘1’ 31 H ADR 0
Device address: ADR (1,0)
D1257 Low ‘0’ 30 H CMD 1
D1257 High ‘2’ 32 H CMD 0
Control parameter: CMD (1,0)
D1258 Low ‘0’ 30 H
D1258 High ‘5’ 35 H
D1259 Low ‘0’ 30 H
D1259 High ‘0’ 30 H
Y0 = H0500
Starting Data Address