Page view 123
8
VFD-B Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-5
Parameters Explanation Settings
Factory
Setting
00: Enable Forward/Reverse operation
01: Disable Reverse operation
02-04 Motor Direction Control
02: Disabled Forward operation
00
00: FWD/STOP, REV/STOP
01: FWD/REV, RUN/STOP
02-05
2-wire/3-wire Operation
Control Modes
02: 3-wire Operation
00
00: Disable
02-06 Line Start Lockout
01: Enable
00
00: Decelerate to 0 Hz
01: Stop immediately and display EF
02-07 Loss of ACI Signal
02: Continue operation by last frequency
command
00
00: Based on Accel/Decel Time
02-08 Up/Down Key Mode
01: Constant speed
00
02-09
The Acce/Decel Speed of
the UP/DOWN Key with
Constant Speed
0.01~1.00 Hz/msec 0.01
00: Digital keypad
01: 0 to +10V from AVI
02: 4 to 20mA from ACI
03: -10 to +10Vdc from AUI
02-10
Source of the Master
Frequency Command
(FCHA)
04: RS-485 communication interface
00
00: Digital keypad
01: 0 to +10V from AVI
02: 4 to 20mA from ACI
03: -10 to +10Vdc from AUI
02-11
Source of the Auxiliary
Frequency Command
(FCHB)
04: RS-485 communication interface
00
00: Master frequency + Auxiliary frequency
02-12
Combination of the Master
and Auxiliary Frequency
Command
01: Master frequency - Auxiliary frequency
00
00: Master Frequency determined by the
digital keypad or external UP/DOWN
keys of the Multi Function Inputs.
01: 0 to +10V from AVI
02: 4 to 20mA from ACI
03: -10 to +10Vdc from AUI
04: RS-485 communication interface
02-13
Source of Second
Frequency Command
05: RS-485 communication interface. It
won’t memorize the frequency.
00
Page view 123