5
VFD-B Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-23
04 - 17
AUI Input Gain
a Factory Setting: 100
Settings 01 to 200% Unit: 1%
04 - 18
No AUI Negative bias command
Factory Setting: 00
Settings 00 No ACI Negative bias command
01 Negative bias, REV motion enabled
02 Negative bias, REV motion disabled
Pr.04-00 ~ 04-03, Pr.04-11 ~ 04-18 are used when the source of frequency command is
the analog signal. Refer to the following examples.
Example 1:
Max.
Output
Freq.
60Hz
Pr.01-00
0Hz
0V
4m
A
5V
12m
A
10V
20m
A
Factory Settings
Pr.01-00=60Hz--Max. output Freq.
Pr.04-11=0%--bias adjustment
Pr.04-12 =0-- bias polarity
Pr.04-13=100% -- pot. freq. gain
Pr.04-14=0 -- REV disable in negative bias
30Hz
Example 2:
In this example with the potentiometer set to 0V the Output Frequency is 10 Hz. The mid-point
of the potentiometer becomes 40 Hz. Once the Maximum Output Frequency is reached any
further increase of the potentiometer will not increase output frequency. (If you want to use the
range of 60Hz, please refer to the example 3.) The value of external input voltage/current
0-8.33V (4-13.33mA) corresponds to the setting frequency 0-60Hz.
Max. Output Freq.
60Hz
Pr.01-00
0Hz
0V
4m
A
5V
12mA
10V
20m
A
Factory Settings
Pr.01-00=60Hz--Max. output Freq.
Pr.04-11=16.7%-- bias adjustment
Pr.04-12=0 -- bias polarity
Pr.04-13=100% -- pot. freq. gain
Pr.04-14=0 -- REV motion disable in negative bias
10Hz
Bias
Adjustment