4.4.1 In-line Connection (Bypassed)
N
NOTE
Models MCD5-0021B - MCD5-0215B are internally bypassed.
Models MCD5-0245C - MCD5-1600C require an exte
rnal
bypass contactor.
A
AC-53b
3-30:330
AC-53b
4-20:340
AC-53b
4.5-30:330
MCD5-0021B 21 A 17 A 15 A
MCD5-0037B 37 A 31 A 26 A
MCD5-0043B 43 A 37 A 30 A
MCD5-0053B 53 A 46 A 37 A
A
AC-53b
3-30:570
AC-53b
4-20:580
AC-53b
4.5-30:570
MCD5-0068B 68 A 55 A 47 A
MCD5-0084B 84 A 69 A 58 A
MCD5-0089B 89 A 74 A 61 A
MCD5-0105B 105 A 95 A 78 A
MCD5-0131B 131 A 106 A 90 A
MCD5-0141B 141 A 121 A 97 A
MCD5-0195B 195 A 160 A 134 A
MCD5-0215B 215 A 178 A 148 A
MCD5-0245C 255 A 201 A 176 A
MCD5-0360C 360 A 310 A 263 A
MCD5-0380C 380 A 359 A 299 A
MCD5-0428C 430 A 368 A 309 A
MCD5-0595C 620 A 540 A 434 A
MCD5-0619C 650 A 561 A 455 A
MCD5-0790C 790 A 714 A 579 A
MCD5-0927C 930 A 829 A 661 A
MCD5-1200C 1200 A 1200 A 1071 A
MCD5-1410C 1410 A 1319 A 1114 A
MCD5-1600C 1600 A 1600 A 1353 A
4.4.2 AC-53 Rating for Bypassed Operation
All ratings are calculated at altitude of 1000 metres and ambient temperature of 40r C.
Electrical Installation MCD 500 Operating Instruction
MG.17.K3.02 - VLT
®