N
NOTE
If the MCD-500 trips on supply frequency (Par. 16-5
Frequency) when the braking contactor KM2 opens, m
odify
the setting of Pars. 2-8 - 2-10.
5.13 Two Speed Motor
The MCD 500 can be configured for control of dual speed
Dahlander type motors, using a high speed contactor (KM1),
low speed contactor (KM2) and a star contactor (KM3).
NOTE
Pole Amplitude Modulated (PAM) motors alter the speed by
effectively changing the stator frequency usi
ng external
winding configuration. Soft starters are not suitable for use
with this type of two-speed m
otor.
When the soft starter receives a high speed start signal, it
closes the high speed contactor (KM1) and star contactor
(KM3), then controls the motor according to the primary
motor settings (par. 1-1 - 1-16.)
When the soft starter receives a low speed start signal, it
closes the low speed contactor (KM2). This closes Input A
and the MCD 500 controls the motor according to the
secondary motor settings (par. 7-1 - 7-16).
177HA527.10
2/T1
4/T2
6/T3
E
T4
T5
T6
T1
T2
T3
A6
A4
A5
1/L1
3/L2
5/L3
24
22
21
KA1
KA2
KA1
KA2
KM3
KA1
KM2KA2
KM1
KM2
KM3
KM1
KM3
KM1
KM3
KM2
S1
KM2
KM1
KA1
F1
17
18
25
11
16
15
3
6
7
5
4
2
1
1
Control voltage KA1 Remote start relay (low speed)
2
Remote control inputs KA2 Remote start relay (high speed)
3
Relay outputs KM1 Line contactor (high speed)
4
3-phase supply KM2 Line contactor (low speed)
5
Motor terminals KM3 Star contactor (high speed)
6
Remote low-speed start input S1 Reset contact
7
Remote high-speed start input 21, 22, 24 Relay output B
Application Examples MCD 500 Operating Instruction
40 MG.17.K3.02 - VLT
®
is a registered Danfoss trademark
55