5-4 Auto-Stop Time
Range: Function:
1 min* [00:01 -
24:00
(hrs:min)]
Sets the time for the soft starter to auto-
stop, in 24 hour clock format.
CAUTION
This function should not be used in
conjunction with remote two-wire
control. The soft starter will sti
ll accept
start and stop commands from the
remote inputs or serial communication
network. To disable loc
al or remote
control, use Par. 3-1 Local/Remote. If
auto-start is enabled and the user is in
the menu sy
stem, auto-start will
become active if the menu times out (if
no keypad activity is detected for five
mi
nutes).
7.9 Auto-Reset
The MCD 500 can be programmed to automatically reset
certain trips, which can help minimise operating downtime.
Trips are divided into three categories for auto-reset,
depending on the risk to the soft starter:
Group
A
Current Imbalance
Phase Loss
Power Loss
Mains Frequency
B
Undercurrent
Instantaneous Overcurrent
Input A Trip
C
Motor Overload
Motor Thermistor
Starter Overtemperature
Other trips cannot be automatically reset.
This function is ideal for remote installations using 2-wire
control in Auto On mode. If the 2-wire start signal is present
after an auto-reset, the MCD 500 will restart.
6-1 Auto-Reset Action
Option: Function:
Selects which trips can be auto-reset.
Do not Auto-Reset
Reset Group A
Reset Group A & B
Reset Group A, B & C
6-2 Maximum Resets
Range: Function:
1* [1 - 5] Sets how many times the soft starter will auto-reset, if
it continues to trip. The reset counter increases by
one each time the soft starter auto-resets, and
6-2 Maximum Resets
Range: Function:
decreases by one after each successful start/stop
cycle.
NOTE
The reset counter will return to 0 if the starter is manually
reset.
7.9.1 Auto-Reset Delay
The MCD 500 can be configured to wait before auto-
resetting a trip. Separate delays can be set for trips in Groups
A and B, or in Group C.
6-3 Reset Delay Groups A & B
Range: Function:
5 secs* [00:05 - 15:00
(min:secs)]
Sets the auto-reset delay for
Group A and Group B trips.
6-4 Reset Delay Group C
Range: Function:
5 min* [5 - 60 (minutes)] Sets the auto-reset delay for Group C
trips.
7.10 Secondary Motor Set
7-1 Motor FLC-2
Range: Function:
[Motor
dependent]
Matches the starter to the second motor's
full load current. Set to the full load current
(FLC) rating shown on the motor nameplate.
7-2 Locked Rotor Time-2
Range: Function:
10 secs* [0:01 - 2:00
(min:secs)]
Sets the maximum length of the time
the motor can run at locked rotor
current from cold before reaching its
maximum temperature. Set according
to the motor datasheet.
If this information is not available, we
recommend the value should be less
than 20 seconds.
7-3 Start Mode-2
Option: Function:
Selects the start mode for the secondary
motor.
Constant Current
Adaptive Control
7-4 Current Limit-2
Range: Function:
350%* [100% - 600%
FLC]
Sets the current limit for constant current
and current ramp soft starting, as a
percentage of motor full load current.
Programming MCD 500 Operating Instruction
MG.17.K3.02 - VLT
®
is a registered Danfoss trademark 57