5.11 Auxiliary Trip Circuit
In normal operation the MCD 500 is controlled via a remote two wire signal (terminals 17, 18).
Input A (terminals 11, 16) is connected to an external trip circuit (such as a low pressure alarm switch for a pumping system).
When the external circuit activates, the soft starter trips, which stops the motor.
KM1
F1
24
VDC
22
21
6/T3
2/T1
13
14
4/T2
24
33
34
06
05
08
07
17
18
25
11
16
A6
A5
A4
5/L3
3/L2
15
S3
S1
S2
E
1/L1
+
+
5
6 7
4
2
A
3
1
177HA525.10
1
Control voltage (model dependent) S1 Start/stop contact
24 VDC output S2 Reset contact
Remote control inputs S3 Auxiliary trip contact
Motor thermistor input (PTC only) 13, 14 Relay output A
Relay outputs 21, 22, 24 Relay output B
3-phase supply 33, 34 Relay output C
Motor terminals
Par. 3-3 Input A Function
Select Input Trip (N/O) assigns the Input A to Auxiliary Trip (N/O) function
Par. 3-4 Input A Name
Select a name e.g. Low Pressure - assigns a name to Input A.
Par. 3-8 Remote Reset Logic
Select as required e.g. Normally Closed - the input behaves like a normally closed contact.
Application Examples MCD 500 Operating Instruction
38 MG.17.K3.02 - VLT
®
is a registered Danfoss trademark
Comments to this Manuals