7.4 Primary Motor Settings
N
NOTE
Default settings are marked with .
The parameters in Primary Motors Settings configure the soft
starter to match the connected motor. These parameters
describe the motor's operating characteristics and allow the
soft starter to model the motor's temperature.
1-1 Motor FLC
Option: Function:
Model
dependent
Matches the starter to the connected motor's
full load current. Set to the full load current
(FLC) rating shown on the motor nameplate.
1-2 Locked Rotor Time
Range: Function:
10 secs* [0:01 - 2:00
(min:sec)]
Sets the maximum length of the time the
motor can run at locked rotor current
from cold before reaching its maximum
temperature. Set according to the motor
datasheet.
If this information is not available, we
recommend the value should be less
than 20 seconds.
1-3 Start Mode
Option: Function:
Selects the soft start mode. See Starting
Modes in chapter Application Examples for
more details.
Constant Current
Adaptive Control
1-4 Current Limit
Range: Function:
350%* [100% -
600% FLC]
Sets the current limit for constant current
and current ramp soft starting, as a
percentage of motor full load current. See
Starting Modes in chapter Application
Examples for more details.
1-5 Initial Current
Range: Function:
350%* [100% -
600% FLC]
Sets the initial start current level for current
ramp starting, as a percentage of motor full
load current. Set so that the motor begins to
accelerate immediately after a start is initiated.
If current ramp starting is not required, set the
initial current equal to the current limit. See
Starting Modes in chapter Application Examples
for more details.
1-6 Start Ramp Time
Range: Function:
10 secs* [1 - 180
secs]
Sets the total start time for an AAC
Adaptive Control start or the ramp time for
current ramp starting (from the initial
current to the current limit). See Starting
Modes in chapter Application Examples for
more details.
1-7 Kickstart Level
Range: Function:
500%* [100% -
700% FLC]
Sets the level of the kickstart current.
CAUTION
Kickstart subjects the mechanical
equipment to increased torque levels.
Ensure the motor, load and coup
lings
can handle the additional torque
before using this feature.
1-8 Kickstart Time
Range: Function:
0000
msecs*
[0 - 2000
msecs]
Sets the kickstart duration. A setting of 0
disables kickstart. See Starting Modes in
chapter Application Examples for more
details.
CAUTION
Kickstart subjects the mechanical
equipment to increased torque levels.
Ensure the motor, load and coup
lings
can handle the additional torque
before using this feature.
1-9 Excess Start Time
Range: Function:
Excess start time is the maximum time
the MCD 500 will attempt to start the
motor. If the motor does not reach full
speed within the programmed limit, the
starter will trip. Set for a period slightly
longer than required for a normal healthy
start. A setting of 0 disables excess start
time protection.
20
secs
*
[0:00 - 4:00
(min:secs)]
Set as required.
1-10 Stop Mode
Option: Function:
Selects the stop mode. See Stopping Modes in
chapter Application Examples for more details.
Coast to Stop
TVR Soft Stop
Adaptive Control
Brake
Programming MCD 500 Operating Instruction
MG.17.K3.02 - VLT
®
is a registered Danfoss trademark 51
7 7