11 Bus Bar Adjustment Procedure (MCD5-0360C - MCD5-1600C)
N
NOTE
Many electronic components are sensitive to static
electricity. Voltages so low that they cannot be fe
lt, seen or
heard, can reduce the life, affect performance, or completely
destroy sensitive electronic
components. When performing
service, proper ESD equipment should be used to prevent
possible damage fro
m occurring.
All units are manufactured with input and output bus bars at the bottom of the unit as standard. The input and/or output bus
bars can be moved tot he top of the unit if required.
Bus Bar Adjustment Procedur... MCD 500 Operating Instruction
MG.17.K3.02 - VLT
®
is a registered Danfoss trademark 73
11 11